3mm Polyurethane food mixing room

Pagefresh SL is a 2 mm heavy duty, chemical resistant antimicrobial treated polyurethane resin floor finish. Attractive smooth matt coloured floor finish

Benefits:

Ideal for dry processing zones such as food packaging zones.

  • Contains Polygiene, an antimicrobial additive based on silver ion technology
  • Cost effective
  • Very high chemical resistance
  • Easy to clean and sterilise – minimal joints
  • Non tainting, non dusting
  • High abrasion resistance
  • Withstands high mechanical stress
  • Low odour during application
FeRFA Resin Flooring guidelines

Description:

Applied in two or more coats. Generally solvent or water borne.

Duty:

light foot traffic, occasional rubber tyred vehicles.

Typical Thickness:

up to 150 µm

Description:

Applied in two or more coats. Generally solvent free.

Duty:

light foot traffic, occasional rubber tyred vehicles/regular foot traffic, frequent fork lift truck traffic, occasional hard plastic-wheeled trolleys

Typical Thickness:

150 µm to 300 µm

Description:

Applied in two or more coats. Generally solvent or water borne.

Duty:

lregular foot traffic, frequent fork lift truck traffic, occasional hard plastic-wheeled trolleys

Typical Thickness:

300 µm to 1000 µm

Description:

Aggregate dressed systems based on multiple layers of floor coatings or flow-applied floorings, often described as ‘sandwich’ systems.
MD/HD

Duty:

regular foot traffic, frequent fork lift truck traffic, occasional hard plastic-wheeled trolleys/constant fork lift truck traffic, hard plastic wheeled trolleys, some impact

Typical Thickness:

> 2 mm

Description:

Often referred to as ‘self-smoothing’ or ‘self-levelling’ flooring and having a smooth surface.

Duty:

regular foot traffic, frequent fork lift truck traffic, occasional hard plastic-wheeled trolleys/constant fork lift truck traffic, hard plastic wheeled trolleys, some impact

Typical Thickness:

2 mm to 3 mm

Description:

Trowel-finished, heavily filled systems, generally incorporating a surface seal coat to minimize porosity.

Duty:

regular foot traffic, frequent fork lift truck traffic, occasional hard plastic-wheeled trolleys/constant fork lift truck traffic, hard plastic wheeled trolleys, some impact

Typical Thickness:

> 4 mm

Description:

Having a smooth surface.

Duty:

constant fork lift truck traffic, hard plastic wheeled trolleys, some impact/severe heavily loaded traffic and impact

Typical Thickness:

4 mm to 6 mm

Description:

Trowel-finished, aggregate filled systems effectively impervious throughout their thickness.

Duty:

severe heavily loaded traffic and impact

Typical Thickness:

> 6 mm

Product: Pagefresh SL

Finish: Matt

Thickness: 2 mm

Colour: Preparatory  work and application  in accordance with suppliers instructions.

Supplier: Page Industrial Coatings Ltd.

Telephone : Customer Service – +44 (0) 1443 475 270

­

Topping: Pagefresh SL (density 1.9 kg/I)

@3.8 kg/m, for 2 mm

Note

Pagefresh SL is not colour fast and may change colour over time (exhibits a yellowing effect). Colour change depends on the UV light and heat levels present and hence the rate of change cannot be predicted. This is more noticeable in light colours and blues but does not compromise the product’s flexibility or chemical resistance characteristics. We have endeavoured to adopt colours within our standard range which minimise this Change.

Installation Service

The installation should be carried out by trained personnel of Page Industrial  Coatings Ltd

Concrete or screed substrate should be a minimum of 25N/mm2 , free from laitance, dust and other contamination. The substrate should be dry to 75% RH as per BS 8204 and free from rising damp and ground water pressure. If no damp proof membrane is present Hydraseal DPM can be incorporated directly beneath the Pagefresh SL system.

Primer: Pageprime @ 0.25 kg/m

OR, where a DPM is required, Hydraseal DPM @ 0.5 kg/m

The finished system is assessed as non-hazardous to health and the environment. The long service life and seam­ less surface reduce the need for repairs, maintenance and cleaning. Environmental and health considerations are controlled during manufacture and application of the products by Page staff and fully trained and experienced contractors.

Page are market leaders in specialist industrial and commercial flooring. Systems available include: underfloor heating systems, floor screeds, surface damp proof mem­branes, decorative floor finishes, seamless terrazzo, car park deck waterproofing, tank lining systems.. . to name just a few. Our objective is to satisfy your Floorzone needs.

The figures that follow are typical properties achieved in laboratory tests at 20 degrees and at 50% Relative Hu­midity.

EN 13813 A1.0-B2.8-I R20.0 Synthetic screed material for use internally in buildings
Reaction to fire Bs S1 (13501-l)
Impact Resistance IR 20.0 (EN ISO 6272)
Wear Resistonce A 1.0 (EN 13892-3)
Boned Strength B2.8 ((EN 13892-8))

 

Slip Resistadlce
Method described in in BS 7976-2 (typical values for 4-S rubber slider)
Dry >40 low slip potential (in accordacnce with I-ISE and UKSRG guidelines)

The slipperiness of flooring materials can change significanlly, due to the installation process, after short periods of use, due to inappropriate maintenance, longer term wear and/ or surface contaminants (wet or dry).

Textured systems are recommended to meet slip resistance value requirements for wet conditions and/ ,or surface contaminants (wet or dry) – please contact our technical Advisors for further details and specifications.

Temperature resistance Tollerant to intermittent spillages up to 120°C or sustained dry heat from -A40°C to 105°C (at 9 mm thickness.)
Water Permeability Nil – Karsten test (impermeable)
Vapour Permeability ASTM E96 :9 0 3g/m’/ 2.4hrs(at 9 mm thick)(impermeable)
Chemical Resistance Contact technical department – excellent resistance to sugars and most acids (organic and inorganic)
Compressive strength > 50 N/mm2 (BS 6319)
Flexural Strength 20 N/mm2 (BS 6319)
Tensile Strength 10 N/mm2 (BS 6319)

Speed Of Cure

10°C 20°C 30°C
Light Traffic 36 hours 24 hours 12 hours
Full Traffic 72 hours 48 hours 24 hours
Full Chemical Cure 10 days 7 days 5 days

Aftercare – Cleaning and Maintenance
Clean regularly using a single or double headed rotary scrubber drier in conjunction with a m ild alkaline detergent.